고객센터
Customer Center
Customer Center
> 고객센터 > QR
ATS:68WN
|
Frame |
68WN | ||||
|
Rated Current(In) |
A |
600 | |||
|
Rated Voltage(Ue) |
V |
AC600 | |||
|
Rated Insulation Voltage(Ui) |
V |
AC800 | |||
|
Rated Impulse Voltage(Uimp) |
kV |
8 | |||
|
Pole |
P |
3,4 | |||
|
Throw |
T |
Double Throw | |||
|
Connection Type |
Front |
● | |||
|
Back |
● | ||||
|
Performance | |||||
|
Short Time Current(1s) lcw |
kA |
15 | |||
|
Short Circuit Peak Current lcm |
kA |
15 | |||
|
With Specific Circuit Breaker |
kA |
42 | |||
|
Fuse Mounting |
kA |
200 | |||
|
Switch Capacity Note1) |
Class |
AC-33B | |||
|
Endurance |
Electrical |
Cycles |
5,000 | ||
|
Mechanical |
Cycles |
10,000 | |||
|
Transfer Sequence |
A↔B, A↔Neutral(off)↔B | ||||
|
Operation Time |
Closing |
msec |
≤100 | ||
|
Trip |
msec |
≤30 | |||
|
Conditions of Uninterruptible Transfer |
3P |
4P | |||
|
Closing |
AC/DC 110V |
A |
8 |
10 | |
|
AC 220V |
A |
4 |
5 | ||
|
Trip Note2) |
AC/DC 110V |
A |
4 | ||
|
AC 220V |
A |
2 | |||
|
Dimensions & Weights | |||||
|
Front Size(mm)
|
H |
278 |
278 | ||
|
| |||||